- Y&Y M618 及Y&Y M668
已取得CE及
SEMKO認證, 認證號碼: 610596
- 本產品適用於長明式或後備式照明系統
- 本產品適用於電子鎮流器或電感鎮流器照明設備
- 工作電壓為 220-240V 50Hz
直流輸出 DC4.8-6V
- 充電時間24小時100% 12小時50%
|
Application:
The modules incorporate 4 pole
change over relays. Therefore, all modules are suitable for Electronic
Ballast (High Frequency Ballast) and Conventional Ballast (Switch Start
Control Gear).
|
-
The circuit shall be suitable
for use at 220V - 240V 50Hz +/- 6%.
-
The module comprises battery
charger, solid state automatic device operating a changeover relay,
deep discharge protection circuit, LED charge indicator and NC test
switch.
-
The method of connection
is by terminal block and a quick release mechanism is fitting so
that leads may easily be removed. Wires of cross sectional area
0.5 - 2.0mm2 may be connected by pushing a solid conductor into
the connection. We only use push connection terminals these not
only give the benefit of fast installation but you cannot over tighten
like you can with screw. This over tightening can cause the connection
to break and some free on delivery to site and thus causing the
product not to work.
-
The red LED is normally continuously
lit and this shows that a charge current is flowing the battery.
The red LED goes out during the un-switched supply cut or the battery
fails. A charge time of 24 hours should be allowed before testing
the unit for its rated duration.
-
Distance between module
and luminaire should be kept to a minimum and must be within 1 metre
for the to be self-contained (BSEN60598-2-22). The luminaire shall
be provided with an integral NC test switch for simulating failure
of the normal supply. Manually operated NC test switch shall be
self-resetting.
-
The unit is confirmed to
provide minimum 3 hours emergency duration upon mains failure.
-
The ambient temperature
range for the module is 0-70°C but in any event the center side
of can should not exceed 70°C
-
The maximum operating temperature
of battery packs is 70°C. This should not be exceeded, or the operational
life of the cells will be reduced. (See our batteries figure for
reference)
-
A battery fuse is incorporated
in the module to protect the battery from heavy discharge.
-
Although the charger is
already short circuit protected it may be desirable for isolation
to include a fuse in the circuit.
-
Linking device is possible
to cover a larger selection of the lamps wiliest still optimizing
the lamps performance by maintaining the battery discharge current
from the battery in its ideal current range.
|
Connection Diagram:
|
|
Technical Data for M6 & M3 Series:
Model |
Y&Y M618 |
Y&Y M668 |
Y&Y M318 |
Y&Y M368 |
Input Voltage |
AC 220V-240V 50Hz +/- 6% single
Phase |
Duration |
3 hrs |
3 hrs |
2 hrs |
2 hrs |
Max. Case Temp. |
70 degrees Centigrade at center
side of case |
Battery |
4 cells |
5 cells |
4 cells |
5 cells |
Nickel Cadmium (Nicd) |
B618EH:
4x4.5 Ah 4.8V |
B668EH:
5x4.5 Ah 6V |
B318:
4x3 Ah 4.8V |
B368:
5x3 Ah 6V |
Nickel Metal Hydride (MH) |
B618MH:
4x4.5 Ah 4.8V |
B668MH:
5x4.5 Ah 6V |
B318MH:
4x3 Ah 4.8V |
B368MH:
5x3 Ah 6V |
Battery Dimensions |
37Wx37Hx275L mm |
37Wx37Hx235L mm |
31Wx31Hx235L mm |
31Wx31Hx285L mm |
31Wx31Hx235L mm |
31Wx31Hx285L mm |
31Wx31Hx192L mm |
31Wx31Hx230L mm |
Battery Charge Current |
0.3A |
0.3A |
0.2A |
0.2A |
Discharge Current |
1.2A |
1.1A |
1.2A |
1.1A |
Charge Indicator |
Red LED |
Recharge Period |
12 hrs For 2 hrs discharge,
24 hrs For 3 hrs discharge |
12 hrs For 1 hrs discharge,
24 hrs For 2 hrs discharge |
Battery Case Temp |
0 - 70 degrees Centigrade |
Ambient Temp |
0 - 70 degrees Centigrade |
Module Size & Weight |
44Wx35Hx150L mm & 250g (140
for Fixing Centres) |
Transfer Time |
< 0.3 second |
Compliance |
EN61347-1:2001, EN61347-2-7 &
EN60925:1991 + A1:1996 + A2:2001 |
BS5266 - Part I, BS5499 - Part III,
IEC60598-2-22, FSD PPA 104(A) 3rd Revision, 850 degrees Centigrade
hot wire test |
|
|
Ballast Lumen Factors for
M6 & M3 Series:
Module \ BLF |
T8
18W |
T8
36W |
T8 58W |
SE 11W |
PLD 13W |
PLD 18W |
PLD 26W |
TE 32W |
TE 42W |
L
18W |
L
24W |
F
18W |
F
24W |
2D 28W |
2D
38W |
Y&Y M618 |
*25% |
15% |
-- |
*41% |
*40% |
*27% |
*25% |
15% |
-- |
*26% |
*24% |
*25% |
*23% |
*23% |
-- |
Y&Y M668 |
*24% |
15% |
12% |
-- |
*42% |
*29% |
*28% |
*26% |
12% |
*30% |
*27% |
*28% |
*26% |
*25% |
*24% |
Y&Y M318 |
*25% |
15% |
-- |
*41% |
*40% |
*27% |
*25% |
15% |
-- |
*26% |
*24% |
*25% |
*23% |
*23% |
-- |
Y&Y M368 |
*24% |
15% |
12% |
-- |
*42% |
*29% |
*28% |
*26% |
12% |
*30% |
*27% |
*28% |
*26% |
*25% |
*24% |
* Link for 5 & 6 Terminals |
|
Technical Data for M2 Series:
Model |
Y&Y M218 |
Y&Y 268 |
Input Voltage |
AC 220V-240V 50Hz +/- 6% single
Phase |
Duration |
2 hrs |
2 hrs |
Max. Case Temp. |
70 degrees Centigrade at center
side of case |
Battery |
5 cells |
5 cells |
Nickel Cadmium (Nicd) |
B218: 5x3 Ah 6V
|
B268: 5x4.5 Ah 6V |
Nickel Metal Hydride (MH) |
B218MH: 5x3 Ah 6V |
B268MH: 5x4.5 Ah 6V |
Battery Dimensions |
31Wx31Hx285L mm |
37Wx37Hx335L mm |
31Wx31Hx230L mm |
31Wx31Hx285L mm |
Battery Charge Current |
0.2A |
0.2A |
Discharge Current |
1.2A |
1.2A |
Charge Indicator |
Red LED |
Recharge Period |
12 hrs For 2 hrs discharge, 24 hrs For 3 hrs discharge |
Battery Case Temp |
0 - 70 degrees Centigrade |
Ambient Temp |
0 - 70 degrees Centigrade |
Module Size & Weight |
44Wx35Hx150L mm & 250g (140
for Fixing Centres) |
Transfer Time |
< 0.3 second |
Compliance |
BS5266 - Part I, BS5499 - Part III, IEC60598-2-22, FSD PPA 104(A)
3rd Revision, 850 degrees Centigrade
hot wire test |
|
|
Ballast Lumen Factors for M2 Series:
Module \ BLF |
T5 14W |
T5 28W |
T5 35W |
Y&Y M218 |
23% |
21% |
- |
Y&Y M268 |
*40% |
24% |
21% |
* Link for 5 & 6 Terminals |
|
Technical Data for M8 Series:
Model |
|
Y&Y M836 |
Y&Y M868 |
Input Voltage |
AC 220V-240V 50Hz +/- 6% single
Phase |
Duration |
2 hrs |
Max. Case Temp. |
70 degrees Centigrade at center
side of case |
Battery |
5 cells |
10 cells |
10 cells |
Nickel Cadmium (Nicd) |
B818:5x3.5 Ah 6V |
B836:10x3 Ah 12V |
B868:10x5 Ah 12V |
Nickel Metal Hydride (MH) |
B818MH:5x3.5 Ah 6V |
B836MH:10x3 Ah 12V |
B868MH:10x5 Ah 12V |
Battery Dimensions |
37Wx37Hx335L mm |
2nos Battery Stick
31Wx31Hx285L mm |
2nos Battery Stick
37Wx37Hx335L mm |
31Wx31Hx285L mm |
2nos Battery Stick
31Wx31Hx230L mm |
2nos Battery Stick
37Wx37Hx285L mm |
Battery Charge Current |
0.6A |
Discharge Current |
3.3A |
Charge Indicator |
Red LED |
Recharge Period |
12 hrs For 2 hrs discharge,
24 hrs For 3 hrs discharge |
Battery Case Temp |
0 - 70 degrees Centigrade |
Ambient Temp |
0 - 70 degrees Centigrade |
Module Size & Weight |
44Wx35Hx150L mm & 250g (140mm
for Fixing Centres) |
48Wx42Hx185L mm & 350g (175mm
for Fixing Centres) |
48Wx42Hx185L mm & 350g (175mm
for Fixing Centres) |
Transfer Time |
< 0.3 second |
Compliance |
BS5266 - Part I, BS5499 - Part III, IEC60598-2-22, FSD PPA 104(A) 3rd Revision, 850 degrees Centigrade
hot wire test |
|
|
Ballast Lumen Factors for M8 Series:
Module \ BLF |
T8 18W |
T8 36W |
T8 58W |
Y&Y M818 |
55% |
- |
- |
Y&Y M836 |
55% |
50% |
- |
Y&Y M868 |
- |
55% |
50% |
* Link for 5 & 6 Terminals |
|
Technical Data For M7 Series:
Model |
|
Y&Y M728 |
Y&Y M735 |
Input Voltage |
AC 220V-240V 50Hz +/- 6% single
Phase |
Duration |
2 hrs |
Max. Case Temp. |
70 degrees Centigrade at center
side of case |
Battery |
5 cells |
10 cells |
10 cells |
Nickel Cadmium (Nicd) |
B818:5x4.5 Ah 6V |
B836:10x3.5 Ah 12V |
B868:10x4 Ah 12V |
Nickel Metal Hydride (MH) |
B818MH:5x4.5 Ah 6V |
B836MH:10x3.5 Ah 12V |
B868MH:10x4 Ah 12V |
Battery Dimensions |
37Wx37Hx335L mm |
2nos Battery Stick
37Wx37Hx335L mm |
2nos Battery Stick
37Wx37Hx335L mm |
31Wx31Hx285L mm |
2nos Battery Stick
31Wx31Hx285L mm |
2nos Battery Stick
37Wx37Hx285L mm |
Battery Charge Current |
0.6A |
Discharge Current |
3.3A |
Charge Indicator |
Red LED |
Recharge Period |
12 hrs For 2 hrs discharge,
24 hrs For 3 hrs discharge |
Battery Case Temp |
0 - 70 degrees Centigrade |
Ambient Temp |
0 - 70 degrees Centigrade |
Module Size & Weight |
44Wx35Hx150L mm & 250g (140mm
for Fixing Centres) |
48Wx42Hx185L mm & 350g (175mm
for Fixing Centres) |
48Wx42Hx185L mm & 350g (175mm
for Fixing Centres) |
Transfer Time |
< 0.3 second |
Compliance |
BS5266 - Part I, BS5499 - Part III,
IEC60598-2-22, FSD PPA 104(A) 3rd Revision, 850 degrees Centigrade
hot wire test |
|
|
Ballast Lumen Factors for M7 Series:
Module \ BLF |
T5 14W |
T5 28W |
T5 35W |
Y&Y M714 |
55% |
- |
- |
Y&Y M728 |
55% |
50% |
- |
Y&Y M735 |
- |
55% |
50% |
* Link for 5 & 6 Terminals |
|
Battery Figure: |
At a temperature of 55 degrees Centigrade , the charge capacity of
normal high temperature cells is 55%,
compared to the charge capacity of the Extra High Temperature Cells
which is over 85%
|
|
|